Customization: | Available |
---|---|
Electricity Type: | Vacuum |
Number of Pole: | 3 |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
HCR-7.2J(D)Y/D315-50T and HCR-12J(D)Y/D200-50T are applicable on AC 50-60Hz power systems, rated voltage 7.2kV and 12kV, rated current 315A, 200A. It can be installed in the switch cabinet to form an F-C circuit and used in conjunction with a comprehensive protector. The Vacuum Contactor Unit combines a high-voltage fuse capable of breaking a wide range of short-circuit fault currents with a vacuum contactor that can be frequently operated. It can be used for frequent starting of motors and frequent switching of transformers and capacitors. Vacuum Contactor-Fuse Combination is widely used in power systems such as power plants, chemicals, coal mines, metallurgy, ports and wharfs. It can be used by power plants and industrial and mining enterprises to switch on and off AC high-voltage motors, transformers, induction furnaces and other loads, and has the function of short-circuit protection. The trolley at the bottom of the Vacuum Contactor-Fuse Combination can be easily moved out of the control cabinet. The altitude of the environment where the product is used does not exceed 1000 meters above sea level.
Technical Data:
Name |
Unit |
Value |
|||||
Main circuit |
Rated working voltage (Ue) |
kV |
7.2 |
12 |
|||
Rated working current (Ie)(Depends on the fuse) |
A |
≤315 |
≤200 |
||||
Rated frequency (fr) |
Hz |
50~60 |
|||||
Rated expected short-circuit breaking current (effective value) |
kA |
≤50 |
|||||
Rated expected short-circuit making current (peak value) |
kA |
125 |
|||||
Power frequency withstand voltage |
Wiring terminal to earth |
kV |
32 |
42 |
|||
Vacuum breaks |
kV |
32 |
42 |
||||
Lightening impulse withstand voltage |
kV |
60 |
75 |
||||
Control circuit |
Rated voltage (Us) |
V |
AC 110/220/380 |
||||
DC 110/220 |
|||||||
Rated power (Ps)electric holding |
VA |
≤1000/100 (absorbing/holding) |
|||||
Rated power (Ps) mechanical holding |
VA |
≤900/600 (Closing/opening) |
|||||
Auxiliary circuit |
Form |
|
(6a+6b) |
||||
Rated value |
|
AC 380V/5A |
|||||
Control circuit, auxiliary circuit to earth power frequency withstand voltage |
kV |
2 |
|||||
Rated operating frequency |
Long-term |
time/h |
300 |
||||
Short-term |
time/h |
600 |
|||||
Mechanical endurance |
10000 times |
30 |
|||||
Electrical endurance |
10000 times |
10(AC-3) |
|||||
Mechanical characteristics |
Closing time |
ms |
≤150 |
||||
3-phase asynchronous time |
ms |
≤3 |
|||||
Original opening time |
ms |
≤150(electric holding), ≤60(mechanical holding) |
|||||
Closing tripping |
ms |
≤4 |
|||||
Remark: 1. rated control voltage can be made according to customer's requirements. |