Feature
Measure 3-phase AC current with high-precision.
Provide LED display and local data query.
Programmable current transformation ratio.
Support RS-485 communications and Modbus-RTU protocol.
Support switch input, switch output and analog output.
Power supply: AC / DC 80V~270V, AC 220V,AC 380V,AC 100V
There are various choices of dimensions to meet the requirements of different electrical circuit enclosure.
Technical Index
Accuracy Measurement
Current class: 0.5
Input Measurement
Wiring 3-phase 3-wire,3-phase 4-wire
Rated value AC 1A,AC 5A
Overload Sustained: 1.2 times; Instantaneous: 10 times/ 5s
Power consumption <0.4VA (per phase)
Impedance <20mΩ
Frequency 45~65Hz
Power supply
Working range A C / D C 8 0 V ~ 2 7 0 V,A C 2 2 0 V,A C 3 8 0 V,A C 1 0 0 V
Power consumption <4VA
Functional Module
Communication interface 1 loop RS-485 Communication, MODBUS-RTU protocol
Baud rate: 2400 ~ 19200bps, Default: 2400bps
Switching value input 4 loops switching value input, dry joint
Switching value output 3 loops relay output, capability: AC 250V/5A,DC 30V/5A
Transmission output 3 loops analog output: 0/4~2 0 m A o r 0~5 / 1 0 V
Environment
Operational environment - 1 0ºC~ + 5 5ºC
Storage environment - 2 5ºC~ + 7 0ºC
Relative humidity ≤9 3 %,in the place without corrosive gas
Height above sea level ≤2 5 0 0 m
Safety
Insulation resistance > 1 0 0 MΩ
AC withstand voltage A C 2 K V
Electro Magnetic Compatibility
Electro-Static discharge class 4
Electrical Fast Transient pulse train class 4
Electrical surge class 4
Outline Dimension
External Dimension( m m ) 120×120;80×80;96×48;96×96;80×80;48×48;120 x 60;160 x 80
Cutout Dimension( m m ) 111×111;76×76;92×45;92×92;68×68;45×45;114 x 56;152 x 76